1 | Stepper motor : motor L4018S1204 -M6 |
---|
2 | WAGO(750-672) |
---|
3 | |
---|
4 | Acctual parameter : |
---|
5 | 24 V control voltage: connect to |
---|
6 | UDC motor voltage: connect to extern alimentation : |
---|
7 | Max tension : 30 V |
---|
8 | Max current : 3 A |
---|
9 | current [0.1A] : 20 |
---|
10 | current_RampUp : 100 |
---|
11 | current_RampDown : 100 |
---|
12 | current_Drive : 50 |
---|
13 | current_Standstill : 33 |
---|
14 | current_stop : 150 |
---|
15 | |
---|
16 | |
---|
17 | Cable connextion : |
---|
18 | x2 8 : output + |
---|
19 | x2 7 : output - |
---|
20 | x2 6 : external alimentation - |
---|
21 | x2 5 : external alimentation - |
---|
22 | x2 4 : motor connector pin 1 |
---|
23 | x2 3 : motor connector pin 2 |
---|
24 | x2 2 : motor connector pin 4 |
---|
25 | x2 1 : motor connector pin 3 |
---|
26 | |
---|
27 | |
---|
28 | |
---|
29 | |
---|
30 | |
---|
31 | Error No.: 1814 |
---|
32 | Designation : TMS_UNDERVOLTAGE_24V |
---|
33 | Description : Undervoltage in the 24V control voltage |
---|
34 | Possible cause/Solution :24 V control voltage shall not exceed 16 V. |
---|
35 | What we have done : Add externe alimentation to 24 V control voltage |
---|
36 | |
---|
37 | |
---|
38 | Error No.: 1816 |
---|
39 | Designation : TMS_UNDERVOLTAGE_V_DC |
---|
40 | Description : Undervoltage in the output voltage supply |
---|
41 | Possible cause/Solution :Output voltage supply shall not be smaller than that configured in parameter 408. |
---|
42 | What we have done : Add externe alimentation to UDC motor voltage |
---|
43 | Turn on alimentation to UDC motor voltage |
---|
44 | under tension on UDC motor voltage |
---|
45 | Issue may appear after a certain time, because motor need more current |
---|
46 | |
---|
47 | Error No.: 1887 |
---|
48 | Designation : TMS_BRIDGE_A_LOW or TMS_BRIDGE_A_LOW_MC3 |
---|
49 | Description : No load detected on motor circuit A |
---|
50 | Possible cause/Solution : Check motor connection. |
---|
51 | What we have done : grow up curent and tension on the alimentation of 24 V control voltage |
---|
52 | |
---|
53 | |
---|
54 | Error No.: 1889 |
---|
55 | Designation : TMS_BRIDGE_B_LOW or TMS_BRIDGE_A_LOW_MC3 |
---|
56 | Description : No load detected on motor circuit B |
---|
57 | Possible cause/Solution : Check motor connection. |
---|
58 | What we have done : grow up curent and tension on the alimentation of UDC motor voltage |
---|
59 | |
---|
60 | |
---|
61 | Error No.: 1363 |
---|
62 | Designation : OPC_TMS_SPI |
---|
63 | Description : Start/selection of an operating mode is not accepted when SPI contact is not present |
---|
64 | Possible cause/Solution : 24 V control voltage dropped |
---|
65 | What we have done : Turn on alimentation |
---|
66 | |
---|
67 | Error No.: 1557 |
---|
68 | Designation : MCALC_PARA_MC3 |
---|
69 | Description :The movement calculator has received invalid parameters |
---|
70 | Possible cause/Solution :Check all parameters acceleration, moving velocity, ramp time, ramp path, ramp type, starting position, target position |
---|
71 | What we have done : Velocity to high (50000) |
---|
72 | |
---|
73 | |
---|
74 | Error No.: 1812 |
---|
75 | Designation : TMS_OVERCURRENT_HW |
---|
76 | Description : Overcurrent output stage(750-673) |
---|
77 | Possible cause/Solution : Overcurrent output stage (750-673): Short circuit or ground leak on the motor circuit |
---|
78 | What we have done : change motor (because the frist one had died) |
---|
79 | |
---|
80 | |
---|
81 | |
---|
82 | |
---|
83 | |
---|
84 | |
---|
85 | |
---|
86 | |
---|
87 | |
---|
88 | |
---|