= First monitored equipment = The first network equipment monitored during the project PowerMon , was an intelligent unit of power distribution (PDU) of mark "PGEP" http://www.pgep.com/, used to distribute electricity to Worker Nodes within LAL's data center .The Web site of the PDU is accessible from LAL's Intranet , with the address: http://pdu-pgep1/ . [[TracNav]] == IP Identification with nslookup == the order: `nslookup pdu-pgep1 `, makes it possible to recover following information: {{{ Server: 134.158.91.80 Address: 134.158.91.80#53 }}} {{{ pdu-pgep1.lal.in2p3.fr canonical name = pc-90178.lal.in2p3.fr. Name: pc-90178.lal.in2p3.fr Address: 134.158.90.178 }}} == SNMP Interrogation == Pdu PGEP1, is an SNMP agent having a downloadable MIB from : http://pdu-pgep1/mib.zip , accessible from LAL's intranet. For example : the shell command: ` snmpwalk -v 1 -c public pdu-pgep1 1.3.6.1.4.1.21239.3.3.1.4 ` returns a series of integers corresponding to ten times (10x) the real consumption measured in amps for each of eight (8) Outlets of circuit 1.