source: ETALON/BPM/motor_error.txt @ 773

Last change on this file since 773 was 773, checked in by moutardier, 6 years ago

add of motor_error.txt that contain information about WAGO 750-672 motor

File size: 2.0 KB
Line 
1Stepper motor : motor L4018S1204 -M6
2                WAGO(750-672)
3
4Acctual parameter :
5        24 V control voltage: connect to
6        UDC  motor voltage: connect to extern alimentation :
7                            Max tension : 30 V
8                            Max current : 3 A
9        current [0.1A] : 20
10        current_RampUp : 100
11        current_RampDown : 100
12        current_Drive : 50
13        current_Standstill : 33
14        current_stop : 150
15
16
17Cable connextion :
18      x2 8 : output +
19      x2 7 : output -
20      x2 6 : external alimentation -
21      x2 5 : external alimentation -
22      x2 4 : motor connector pin 1
23      x2 3 : motor connector pin 2
24      x2 2 : motor connector pin 4
25      x2 1 : motor connector pin 3
26
27
28
29
30
31Error No.: 1814
32Designation : TMS_UNDERVOLTAGE_24V
33Description : Undervoltage in the 24V control voltage
34Possible cause/Solution :24 V control voltage shall not exceed 16 V.
35What we have done : Add externe alimentation to 24 V control voltage
36
37
38Error No.: 1816
39Designation : TMS_UNDERVOLTAGE_V_DC
40Description : Undervoltage in the output voltage supply
41Possible cause/Solution :Output voltage supply shall not be smaller than that configured in parameter 408.
42What we have done : Add externe alimentation to UDC motor voltage
43                    Turn on alimentation to UDC motor voltage
44
45Error No.: 1887
46Designation : TMS_BRIDGE_A_LOW or TMS_BRIDGE_A_LOW_MC3
47Description : No load detected on motor circuit A
48Possible cause/Solution : Check motor connection.
49What we have done : grow up curent and tension on the alimentation of 24 V control voltage
50
51
52Error No.: 1889
53Designation : TMS_BRIDGE_B_LOW or TMS_BRIDGE_A_LOW_MC3
54Description : No load detected on motor circuit B
55Possible cause/Solution : Check motor connection.
56What we have done : grow up curent and tension on the alimentation of UDC motor voltage
57
58
59Error No.: 1363
60Designation : OPC_TMS_SPI
61Description : Start/selection of an operating mode is not accepted when SPI contact is not present
62Possible cause/Solution : 24 V control voltage dropped
63What we have done : Turn on alimentation
64
65
66
67
68
69
70
71
72
73
74
75Error No.:
76Designation :
77Description :
78Possible cause/Solution :
79What we have done :
80