wiki:InfosDiverses

First monitored equipment

The first network equipment monitored during the project PowerMon , was an intelligent unit of power distribution (PDU) of mark "PGEP" http://www.pgep.com/, used to distribute electricity to Worker Nodes within LAL's data center .The Web site of the PDU is accessible from LAL's Intranet , with the address: http://pdu-pgep1/ .

IP Identification with nslookup

the order: nslookup pdu-pgep1 , makes it possible to recover following information:

Server:         134.158.91.80
Address:        134.158.91.80#53
pdu-pgep1.lal.in2p3.fr  canonical name = pc-90178.lal.in2p3.fr.
Name:   pc-90178.lal.in2p3.fr
Address: 134.158.90.178 

SNMP Interrogation

Pdu PGEP1, is an SNMP agent having a downloadable MIB from : http://pdu-pgep1/mib.zip , accessible from LAL's intranet.

For example : the shell command: snmpwalk -v 1 -c public pdu-pgep1 1.3.6.1.4.1.21239.3.3.1.4 returns a series of integers corresponding to ten times (10x) the real consumption measured in amps for each of eight (8) Outlets of circuit 1.

Last modified 14 years ago Last modified on Jul 12, 2010, 12:23:18 PM